Federal Pacific (FPE) and Zinsco panels: what the record shows
If an inspector, insurer or neighbor has told you your panel is “one of those,” here is what the public record actually says. The two brands are not in the same position.
Short answer
Federal Pacific Stab-Lok: the U.S. Consumer Product Safety Commission (CPSC) investigated these breakers from 1980 to 1983. Its testing confirmed they failed certain UL calibration tests, the tests that check whether a breaker trips when it should. CPSC closed the investigation in 1983 without issuing a recall, and later clarified that closing it was not a determination that the breakers are safe.
Zinsco: commonly flagged by home inspectors, but we found no comparable CPSC investigation or finding. The public record is weaker than for FPE.
How to tell whether you have one
Look at the label inside the panel door, without removing the cover. Federal Pacific panels are marked Federal Pacific Electric or FPE, and the breakers and labels often say Stab-Lok. Zinsco panels are labeled Zinsco or Sylvania-Zinsco. If the label is missing or unreadable, a home inspection report or an electrician can identify it. Please don’t open the panel cover yourself.
Federal Pacific Stab-Lok: what CPSC found
| When | What happened |
|---|---|
| June 1980 | The investigation began after FPE’s parent company reported that many FPE breakers did not fully comply with Underwriters Laboratories (UL) requirements. |
| 1980–1983 | CPSC testing “confirmed that these breakers fail certain UL calibration test requirements.” Those tests check whether a breaker holds its rated current and trips within set time limits on overload. The work focused mainly on 2-pole residential breakers made before 1979. |
| March 1983 | CPSC closed the investigation. It cited its limited budget, other hazards it had to address, and the uncertain results of a costly further study. It said it could not yet link the test failures to a hazardous situation, and that it could reopen the investigation if warranted. No recall was issued. |
| 2011 revision | CPSC added a note: the investigation was closed “without making a determination as to the safety of FPE circuit breakers or the accuracy of the manufacturer’s position on the matter.” |
Source: U.S. CPSC, Commission Closes Investigation of FPE Circuit Breakers and Provides Safety Information for Consumers (originally issued March 3, 1983; revised February 18, 2011).
Were Federal Pacific panels recalled?
No. CPSC closed its investigation without a recall. That is not the same as a clean bill of health. In CPSC’s own words, it made no determination either way about the breakers’ safety. So the accurate summary is: documented failures in CPSC testing, and no recall was issued.
Zinsco: what’s documented
Zinsco panels are frequently called out in home inspection reports. The concerns inspectors describe include breakers that may not trip reliably and breakers that can stick or fuse to the panel’s bus bar. These concerns come mainly from the home-inspection and insurance industries.
We found no CPSC investigation, test findings or recall for Zinsco comparable to the FPE record. That doesn’t mean a particular Zinsco panel is fine. It means the evidence is of a different kind, and the condition of your specific panel matters most.
The evidence side by side
| Federal Pacific (Stab-Lok) | Zinsco | |
|---|---|---|
| Federal investigation | Yes. CPSC, 1980–1983 | None found |
| Test findings | CPSC testing confirmed failures of certain UL calibration tests | No comparable public test findings |
| Recall | No. CPSC closed its investigation without one. | None found (CPSC search, September 2026) |
| Main source of concern | CPSC record, plus inspection-industry reports | Home-inspection and insurance-industry reports |
What to do if you have one
- Don’t panic, and don’t ignore it. Treat it as a reason to have the panel properly evaluated, not as proof that it will fail.
- Watch for warning signs such as heat, a burning smell, buzzing, scorch marks or breakers that won’t reset. If you see any, get an evaluation soon. See warning signs.
- Get the panel evaluated for condition, capacity and your future plans. If it’s being replaced anyway, that’s the right time to decide whether the service size should change.
- Ask your insurer how it treats these panels. Practices vary by company.
Many owners choose to replace these panels because of the FPE record, parts availability, insurer questions and peace of mind. Those are reasonable reasons. None of them is a legal requirement we can point to.
Good practice with any breaker panel
CPSC’s advice applies to all breakers and fuses. Don’t just reset a breaker that keeps tripping. Find out why, because it’s often a sign of an overloaded circuit. When in doubt, consult a licensed electrician.